No registers found, Page Number 4-13

Variable Area (Setting Range) List (Page 5-2)

type description address in Hex address in decimal parameter name settings / range level default
FC 03 / FC 16 Process Value (PV) 2000 8192 PV Temperature/Analog specific range (See manual) Operation
FC 03 / FC 16 Status 2001 8193 Status 12 Refer to 5-2 Status for details Operation
FC 03 / FC 16 Internal Set Point 2002 8194 Internal Set Point *1 SP lower limit to SP upper limit Operation
FC 03 / FC 16 Heater Current 1 Value Monitor 2003 8195 Heater Current 1 Value Monitor 0.0 to 55.0 (H'00000000 to H'00000226) Operation
FC 03 / FC 16 MV Monitor (Heating) 2004 8196 MV Monitor (Heating) -5.0 to 105.0 (Standard: HFFFFFFCE to H'0000041A) Operation
FC 03 / FC 16 MV Monitor (Cooling) 2005 8197 MV Monitor (Cooling) 0.0 to 105.0 (Heating/Cooling: H'00000000 to H'0000041A) Operation
FC 03 / FC 16 Set Point 2103 8451 Set Point SP lower limit to SP upper limit Operation
FC 03 / FC 16 Alarm Value 1 2104 8452 Alarm Value 1 -1999 to 9999 (HFFFFFF831 to H'0000270F) Operation
FC 03 / FC 16 Alarm Value Upper Limit 1 2105 8453 Alarm Value Upper Limit 1 -1999 to 9999 (HFFFFFF831 to H'0000270F) Operation
FC 03 / FC 16 Alarm Value Lower Limit 1 2106 8454 Alarm Value Lower Limit 1 -1999 to 9999 (HFFFFFF831 to H'0000270F) Operation
FC 03 / FC 16 Alarm Value 2 2107 8455 Alarm Value 2 -1999 to 9999 (HFFFFFF831 to H'0000270F) Operation
FC 03 / FC 16 Alarm Value Upper Limit 2 2108 8456 Alarm Value Upper Limit 2 -1999 to 9999 (HFFFFFF831 to H'0000270F) Operation
FC 03 / FC 16 Alarm Value Lower Limit 2 2109 8457 Alarm Value Lower Limit 2 -1999 to 9999 (HFFFFFF831 to H'0000270F) Operation
FC 03 / FC 16 Process Value (PV) 2402 9218 PV Temperature/Analog specific range (See manual) Operation
FC 03 / FC 16 Internal Set Point 2403 9219 Internal Set Point *1 SP lower limit to SP upper limit Operation
FC 03 / FC 16 Multi-SP No. Monitor 2404 9220 Multi-SP No. Monitor 0 to 7 (H'00000000 to H'00000007) Operation
FC 03 / FC 16 Status 2406 9222 Status 12 Refer to 5-2 Status for details Operation
FC 03 / FC 16 Status 2407 9223 Status *3 Refer to 5-2 Status for details Operation
FC 03 / FC 16 Status 2 2408 9224 Status 2 12 Refer to 5-2 Status for details Operation
FC 03 / FC 16 Status 2 2409 9225 Status 2 13 Refer to 5-2 Status for details Operation
FC 03 / FC 16 Decimal Point Monitor 2410 9232 Decimal Point Monitor 0 to 3 (H'00000000 to H'00000003) Operation

Variable Area (Setting Range) List (Page 5-3)

type description address in Hex address in decimal parameter name settings / range level default
holding register Operation/Adjustment Protect H'0500 2500 Operation/Adjustment Protect H'00000000 (0): No restrictions in operation and adjustment levels
H'00000001 (1): Move to adjustment level is prohibited.
H'00000002 (2): Display and change of only "PV" and "PV/SP" parameters is allowed.
H'00000003 (3): Display of only "PV" and "PV/SP" parameters is allowed.
Protect H'00000000
holding register Initial Setting/Communications Protect H'0502 2501 Initial Setting/Comm Protect H'00000000 (0): Move to initial setting/communications setting level is allowed. (Move to advanced function setting level is displayed.)
H'00000001 (1): Move to initial setting/communications setting level is allowed. (Move to advanced function setting level is not displayed.)
H'00000002 (2): Move to initial setting/communications setting level is prohibited.
H'00000000
holding register Setting Change Protect H'0504 2502 Setting Change Protect H'00000000 (0): OFF (Changing of setup on controller display is allowed.)
H'00000001 (1): ON (Changing of setup on controller display is prohibited.)
H'00000000
holding register PF Key Protect H'0506 2503 PF Key Protect H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000
holding register Move to Protect Level H'0508 2504 Move to Protect Level H'FFFFF831 to H'0000270F (-1999 to 9999)
holding register Password to Move to Protect Level H'050A 2505 Password to Move Protect Lvl H'FFFFF831 to H'0000270F (-1999 to 9999) (Can only be set. The monitor value is always H'00000000.) H'00000000
holding register Parameter Mask Enable H'050C 2506 Parameter Mask Enable H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000
holding register Changed Parameters Only H'050E 2507 Changed Parameters Only H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000
holding register Manual MV H'0600 2600 Manual MV Standard Models:
Standard control: H'FFFFFCE to H'0000041A (-5.0 to 105.0)
Heating and cooling control: H'FFFFFBE6 to H'0000041A (-105.0 to 105.0)
Position-proportional Models:
Close position-proportional control with the Direct Setting of Position Proportional MV parameter set to ON: H'FFFFFCE to H'0000041A (-5.0 to 105.0)
Manual control
holding register Set Point H'0602 2601 Set Point SP lower limit to SP upper limit Operation
holding register Remote SP Monitor H'0604 2602 Remote SP Monitor Remote SP lower limit -10% FS to Remote SP upper limit +10% FS
holding register Heater Current 1 Value Monitor H'0608 2604 Heater Current 1 Value Mon H'00000000 to H'00000226 (0.0 to 55.0)
holding register MV Monitor (Heating) H'060A 2605 MV Monitor (Heating) Standard control: H'FFFFFCE to H'0000041A (-5.0 to 105.0)
Heating and cooling control: H'00000000 to H'0000041A (0.0 to 105.0)
holding register MV Monitor (Cooling) H'060C 2606 MV Monitor (Cooling) H'00000000 to H'0000041A (0.0 to 105.0)
holding register Valve Opening Monitor H'060E 2607 Valve Opening Monitor H'FFFFF9C to H'0000044C (-10.0 to 110.0)

Communications Data for Modbus (Page 5-4)

type description address in Hex address in decimal parameter name settings / range level default
Read/Write Holding Register Proportional Band (Cooling) 0701 1793 Proportional Band (Cooling) H'00000001 to H'0000270F (0.1 to 999.9) Adjustment
Read/Write Holding Register Integral Time (Cooling) 0702 1794 Integral Time (Cooling) H'00000000 to H'0000270F (0 to 9999: Integral/derivative time unit is 1 s.) (0.0 to 999.9: Integral/derivative time unit is 0.1 s.) Adjustment
Read/Write Holding Register Derivative Time (Cooling) 0703 1795 Derivative Time (Cooling) H'00000000 to H'0000270F (0 to 9999: Integral/derivative time unit is 1 s.) (0.0 to 999.9: Integral/derivative time unit is 0.1 s.) Adjustment
Read/Write Holding Register Dead Band 0704 1796 Dead Band H'FFFFF831 to H'0000270F (-199.9 to 999.9 for temperature input) (-19.99 to 99.99 for analog input) Adjustment
Read/Write Holding Register Manual Reset Value 0705 1797 Manual Reset Value H'00000000 to H'000003E8 (0.0 to 100.0) Adjustment
Read/Write Holding Register Hysteresis (Heating) 0706 1798 Hysteresis (Heating) H'00000001 to H'0000270F (0.1 to 999.9 for temperature input) (0.01 to 99.99 for analog input) Adjustment
Read/Write Holding Register Hysteresis (Cooling) 0707 1799 Hysteresis (Cooling) H'00000001 to H'0000270F (0.1 to 999.9 for temperature input) (0.01 to 99.99 for analog input) Adjustment
Read/Write Holding Register Control Period (Heating) 0708 1800 Control Period (Heating) H'FFFFFFFE (-2): 0.1 s H'FFFFFFFF (-1): 0.2 s H'00000000 (0): 0.5 s H'00000001 to H'00000063 (1 to 99) Initial setting
Read/Write Holding Register Control Period (Cooling) 0709 1801 Control Period (Cooling) H'FFFFFFFE (-2): 0.1 s H'FFFFFFFF (-1): 0.2 s H'00000000 (0): 0.5 s H'00000001 to H'00000063 (1 to 99) Initial setting
Read/Write Holding Register Position Proportional Dead Band 070A 1802 Position Proportional Dead Band H'00000001 to H'00000064 (0.1 to 10.0) Adjustment
Read/Write Holding Register Open/Close Hysteresis 070B 1803 Open/Close Hysteresis H'00000001 to H'000000C8 (0.1 to 20.0) Adjustment
Read/Write Holding Register SP Ramp Time Unit 070C 1804 SP Ramp Time Unit H'00000000 (0): EU/second H'00000001 (1): EU/minute H'00000002 (2): EU/hour Advanced function setting
Read/Write Holding Register SP Ramp Set Value 070D 1805 SP Ramp Set Value H'00000000 (0): OFF H'00000001 to H'0000270F (1 to 9999) Adjustment
Read/Write Holding Register SP Ramp Fall Value 070E 1806 SP Ramp Fall Value H'FFFFFFFF (-1): Same (Same as SP Ramp Set Value.) H'00000000 (0): OFF H'00000001 to H'0000270F (1 to 9999) Adjustment
Read/Write Holding Register MV at Stop 070F 1807 MV at Stop Standard Models: Standard control: H'FFFFFCE to H'0000041A (-5.0 to 105.0) Heating and cooling control: H'FFFFFBE6 to H'0000041A (-105.0 to 105.0) Position-proportional Models: Close position-proportional control with the Direct Setting of Position Proportional MV parameter set to ON: H'FFFFFCE to H'0000041A (-5.0 to 105.0) Floating position-proportional control or the Direct Setting of Position Proportional MV parameter set to OFF: H'FFFFFFFF to H'00000001 (-1 to 1) Adjustment
Read/Write Holding Register MV at PV Error 0711 1809 MV at PV Error Same as MV at Stop parameter Adjustment
Read/Write Holding Register MV Change Rate Limit 0713 1811 MV Change Rate Limit H'00000000 to H'000003E8 (0.0 to 100.0) Operation
Read/Write Holding Register PV Input Slope Coefficient 0718 1816 PV Input Slope Coefficient H'00000001 to H'0000270F (0.001 to 9.999) Operation
Read/Write Holding Register Heater Current 1 Value Monitor 071A 1818 Heater Current 1 Value Monitor H'00000000 to H'00000226 (0.0 to 55.0) Operation
Read/Write Holding Register Heater Burnout Detection 1 071B 1819 Heater Burnout Detection 1 H'00000000 to H'000001F4 (0.0 to 50.0) Adjustment
Read/Write Holding Register Leakage Current 1 Monitor 071C 1820 Leakage Current 1 Monitor H'00000000 to H'00000226 (0.0 to 55.0) Operation
Read/Write Holding Register HS Alarm 1 071D 1821 HS Alarm 1 H'00000000 to H'000001F4 (0.0 to 50.0) Adjustment
Read/Write Holding Register Process Value Input Shift 0723 1827 Process Value Input Shift H'FFFFF831 to H'0000270F (-1999 to 9999) Adjustment
Read/Write Holding Register Heater Current 2 Value Monitor 0724 1828 Heater Current 2 Value Monitor H'00000000 to H'00000226 (0.0 to 55.0) Operation

Variable Area (Setting Range) List (Page 5-5)

type description address in Hex address in decimal parameter name settings / range level default
Write Holding Register (FC 06/16) Heater Burnout Detection 2 2725 10021 Heater Burnout Detection 2 H'00000000 to H'000001F4 (0.0 to 50.0) Adjustment
Write Holding Register (FC 06/16) Leakage Current 2 Monitor 2726 10022 Leakage Current 2 Monitor H'00000000 to H'00000226 (0.0 to 55.0) Operation
Write Holding Register (FC 06/16) HS Alarm 2 2727 10023 HS Alarm 2 H'00000000 to H'000001F4 (0.0 to 50.0) Adjustment
Write Holding Register (FC 06/16) Soak Time Remain 2728 10024 Soak Time Remain H'00000000 to H'0000270F (0 to 9999) Operation
Write Holding Register (FC 06/16) Soak Time 2729 10025 Soak Time H'00000001 to H'0000270F (1 to 9999) Adjustment
Write Holding Register (FC 06/16) Wait Band 272A 10026 Wait Band H'00000000 (0): OFF, H'00000001 to H'0000270F (0.1 to 999.9 for Temp input / 0.01 to 99.99 for Analog input) Adjustment OFF
Write Holding Register (FC 06/16) Remote SP Input Shift 272B 10027 Remote SP Input Shift H'FFFFF831 to H'0000270F (-1999 to 9999) Advanced function setting
Write Holding Register (FC 06/16) Remote SP Input Slope Coefficient 272C 10028 Remote SP Input Slope Coefficient H'00000001 to H'0000270F (0.001 to 9.999) Advanced function setting
Write Holding Register (FC 06/16) Input Digital Filter 2800 10240 Input Digital Filter H'00000000 to H'0000270F (0.0 to 999.9) Advanced function setting
Write Holding Register (FC 06/16) Moving Average Count 2804 10244 Moving Average Count H'00000000 (0): OFF, H'00000001 (1): 2 times, H'00000002 (2): 4 times, H'00000003 (3): 8 times, H'00000004 (4): 16 times, H'00000005 (5): 32 times Advanced function setting OFF

Communications Data for Modbus (Page 5-6)

type description address in Hex address in decimal parameter name settings / range level
Holding Register Extraction of Square Root Low-cut Point 2808 10248 Extraction of Square Root Low-cut Point H'00000000 to H'000003E8 (0.0 to 100.0) Adjustment
Holding Register SP 0 2900 10496 SP 0 SP lower limit to SP upper limit Operation
Holding Register Alarm Value 1 2902 10498 Alarm Value 1 H'FFFFF831 to H'0000270F (-1999 to 9999) Operation
Holding Register Alarm Value Upper Limit 1 2903 10499 Alarm Value Upper Limit 1 H'FFFFF831 to H'0000270F (-1999 to 9999) Operation
Holding Register Alarm Value Lower Limit 1 2904 10500 Alarm Value Lower Limit 1 H'FFFFF831 to H'0000270F (-1999 to 9999) Operation
Holding Register Alarm Value 2 2905 10501 Alarm Value 2 H'FFFFF831 to H'0000270F (-1999 to 9999) Operation
Holding Register Alarm Value Upper Limit 2 2906 10502 Alarm Value Upper Limit 2 H'FFFFF831 to H'0000270F (-1999 to 9999) Operation
Holding Register Alarm Value Lower Limit 2 2907 10503 Alarm Value Lower Limit 2 H'FFFFF831 to H'0000270F (-1999 to 9999) Operation
Holding Register Alarm Value 3 2908 10504 Alarm Value 3 H'FFFFF831 to H'0000270F (-1999 to 9999) Operation
Holding Register Alarm Value Upper Limit 3 2909 10505 Alarm Value Upper Limit 3 H'FFFFF831 to H'0000270F (-1999 to 9999) Operation
Holding Register Alarm Value Lower Limit 3 290A 10506 Alarm Value Lower Limit 3 H'FFFFF831 to H'0000270F (-1999 to 9999) Operation
Holding Register Alarm Value 4 290B 10507 Alarm Value 4 H'FFFFF831 to H'0000270F (-1999 to 9999) Operation
Holding Register Alarm Value Upper Limit 4 290C 10508 Alarm Value Upper Limit 4 H'FFFFF831 to H'0000270F (-1999 to 9999) Operation
Holding Register Alarm Value Lower Limit 4 290D 10509 Alarm Value Lower Limit 4 H'FFFFF831 to H'0000270F (-1999 to 9999) Operation
Holding Register SP 1 290E 10510 SP 1 SP lower limit to SP upper limit Adjustment
Holding Register SP 2 291C 10524 SP 2 SP lower limit to SP upper limit Adjustment
Holding Register SP 3 292A 10538 SP 3 SP lower limit to SP upper limit Adjustment
Holding Register SP 4 2938 10552 SP 4 SP lower limit to SP upper limit Adjustment
Holding Register SP 5 2946 10566 SP 5 SP lower limit to SP upper limit Adjustment
Holding Register SP 6 2954 10580 SP 6 SP lower limit to SP upper limit Adjustment
Holding Register SP 7 2962 10594 SP 7 SP lower limit to SP upper limit Adjustment
Holding Register Proportional Band 2A00 10752 Proportional Band H'00000001 to H'0000270F (0.1 to 999.9) Adjustment
Holding Register Integral Time 2A01 10753 Integral Time Standard, heating/cooling, or close position proportional control: H'00000000 to H'0000270F (0 to 9999: Integral/derivative time unit is 1 s.) (0.0 to 999.9: Integral/derivative time unit is 0.1 s.) Floating position-proportional control: H'00000001 to H'0000270F (1 to 9999: Integral/derivative time unit is 1 s.) (0.1 to 999.9: Integral/derivative time unit is 0.1 s.) Adjustment
Holding Register Derivative Time 2A02 10754 Derivative Time H'00000000 to H'0000270F (0 to 9999: Integral/derivative time unit is 1 s.) (0.0 to 999.9: Integral/derivative time unit is 0.1 s.) Adjustment
Holding Register MV Upper Limit 2A05 10757 MV Upper Limit Standard control or close position-proportional control: MV lower limit + 0.1 to H'0000041A (MV lower limit + 0.1 to 105.0) Heating and cooling control: H'00000000 to H'0000041A (0.0 to 105.0) Adjustment
Holding Register MV Lower Limit 2A06 10758 MV Lower Limit Standard control or close position-proportional control: H'FFFFFFCE to MV upper limit -0.1 (-5.0 to MV upper limit -0.1) Heating and cooling control: H'FFFFFBE6 to H'00000000 (-105.0 to 0.0) Adjustment

Modbus Registers (Page 5-7)

type description address in Hex address in decimal parameter name settings / range level default
03/06/16 Input Type 2C00 11264 Input Type H'00000000 (0): Pt (-200 to 850°C/-300 to 1500°F)
H'00000001 (1): Pt (-199.9 to 500.0°C/-199.9 to 900.0°F)
H'00000002 (2): Pt (0.0 to 100.0°C/0.0 to 210.0°F)
H'00000003 (3): JPt (-199.9 to 500.0°C/-199.9 to 900.0°F)
H'00000004 (4): JPt (0.0 to 100.0°C/0.0 to 210.0°F)
H'00000005 (5): K (-200 to 1300°C/-300 to 2300°F)
H'00000006 (6): K (-20.0 to 500.0°C/0.0 to 900.0°F)
H'00000007 (7): J (-100 to 850°C/-100 to 1500°F)
H'00000008 (8): J (-20.0 to 400.0°C/0.0 to 750.0°F)
H'00000009 (9): T (-200 to 400°C/-300 to 700°F)
H'0000000A (10): T (-199.9 to 400.0°C/-199.9 to 700.0°F)
H'0000000B (11): E (-200 to 600°C/-300 to 1100°F)
H'0000000C (12): L (-100 to 850°C/-100 to 1500°F)
H'0000000D (13): U (-200 to 400°C/-300 to 700°F)
H'0000000E (14): U (-199.9 to 400.0°C/-199.9 to 700.0°F)
H'0000000F (15): N (-200 to 1300°C/-300 to 2300°F)
H'00000010 (16): R (0 to 1700°C/0 to 3000°F)
H'00000011 (17): S (0 to 1700°C/0 to 3000°F)
H'00000012 (18): B (100 to 1800°C/300 to 3200°F)
H'00000013 (19): W (0 to 2,300°C/0 to 3,200°F)
H'00000014 (20): PLII (0 to 1,300°C/0 to 2,300°F)
H'00000015 (21): Infrared temperature sensor (K 140°F/60°C)
H'00000016 (22): Infrared temperature sensor (K 240°F/120°C)
H'00000017 (23): Infrared temperature sensor (K 280°F/140°C)
H'00000018 (24): Infrared temperature sensor (K 440°F/220°C)
H'00000019 (25): 4 to 20 mA
H'0000001A (26): 0 to 20 mA
H'0000001B (27): 1 to 5 V
H'0000001C (28): 0 to 5 V
H'0000001D (29): 0 to 10 V
H'0000001E (30): 0 to 50 mV
Initial setting
03/06/16 Temperature Unit 2C01 11265 Temperature Unit H'00000000 (0): °C
H'00000001 (1): °F
03/06/16 Scaling Lower Limit 2C09 11273 Scaling Lower Limit H'FFFFF831 to scaling upper limit 1
(1999 to scaling upper limit 1)
03/06/16 Scaling Upper Limit 2C0B 11275 Scaling Upper Limit Scaling lower limit + 1 to H'0000270F
(Scaling lower limit + 1 to 9999)
03/06/16 Decimal Point 2C0C 11276 Decimal Point H'00000000 to 00000003 (0 to 3)
03/06/16 Remote SP Upper limit 2C0D 11277 Remote SP Upper limit Input range lower limit to Input range upper limit for temperature input
Scaling lower limit to Scaling upper limit for analog input
Advanced function setting
03/06/16 Remote SP Lower limit 2C0E 11278 Remote SP Lower limit Input range lower limit to Input range upper limit for temperature input
Scaling lower limit to Scaling upper limit for analog input
Advanced function setting
03/06/16 PV Decimal Point Display 2C0F 11279 PV Decimal Point Display H'00000000 (0): OFF
H'00000001 (1): ON
03/06/16 Control Output 1 Signal 2D03 11523 Control Output 1 Signal H'00000000 (0): 4 to 20 mA
H'00000001 (1): 0 to 20 mA
Initial setting
03/06/16 Control Output 2 Signal 2D04 11524 Control Output 2 Signal H'00000000 (0): 4 to 20 mA
H'00000001 (1): 0 to 20 mA
03/06/16 SP Upper Limit 2D0F 11535 SP Upper Limit The range of values (without decimal point) is as follows:
Temperature input: SP lower limit + 1 to Input range upper limit
Analog input: SP lower limit + 1 to Scaling upper limit
03/06/16 SP Lower Limit 2D10 11536 SP Lower Limit The range of values (without decimal point) is as follows:
Temperature input: Input range lower limit to SP upper limit - 1
Analog input: Scaling lower limit to SP upper limit - 1
03/06/16 Standard or Heat/Cool 2D11 11537 Standard or Heating/Cooling H'00000000 (0): Standard
H'00000001 (1): Heating and cooling
Initial setting

Communications Data for Modbus (Page 5-8)

type description address in Hex address in decimal parameter name settings / range level
Holding Register (Read/Write) Direct/Reverse Operation 2D12 11538 Direct/Reverse Operation H'00000000 (0): Reverse operation H'00000001 (1): Direct operation Initial setting
Holding Register (Read/Write) Close/Floating 2D13 11539 Close/Floating H'00000000 (0): Floating H'00000001 (1): Close
Holding Register (Read/Write) PID ON/OFF 2D14 11540 PID ON/OFF H'00000000 (0): ON/OFF H'00000001 (1): 2 PID control
Holding Register (Read/Write) ST 2D15 11541 ST H'00000000 (0): OFF H'00000001 (1): ON
Holding Register (Read/Write) Program Pattern 2D16 11542 Program Pattern H'00000000 (0): OFF H'00000001 (1): STOP H'00000002 (2): CONT
Holding Register (Read/Write) Remote SP Input 2D18 11544 Remote SP Input H'00000000 (0): 4 to 20 mA H'00000001 (1): 0 to 20 mA H'00000002 (2): 1 to 5 V H'00000003 (3): 0 to 5 V H'00000004 (4): 0 to 10 V Advanced function setting
Holding Register (Read/Write) Minimum Output ON/OFF Band 2D19 11545 Minimum Output ON/OFF Band H'00000000 to H'000001F4 (0.0 to 50.0)
Holding Register (Read/Write) Transfer Output Type 2E00 11776 Transfer Output Type H'00000000 (0): OFF H'00000001 (1): Set point H'00000002 (2): Set point during SP ramp H'00000003 (3): PV H'00000004 (4): MV (heating) H'00000005 (5): MV (cooling) ... Initial setting
Holding Register (Read/Write) Transfer Output Signal 2E01 11777 Transfer Output Signal H'00000000 (0): 4 to 20 mA H'00000001 (1): 1 to 5 V

Communications Data for Modbus (Page 5-9)

type description address in Hex address in decimal parameter name settings / range level default
write holding register Control Output 1 Assignment parameter 0x2E06 11782 Control Output 1 Assignment Relay/Voltage Output: H'00000000 (0) to H'00000016 (22)
(0: Not assigned, 1: Ctrl output (heating), 2: Ctrl output (cooling), 3: Alarm 1, 4: Alarm 2, 5: Alarm 3, 6: Alarm 4, 7: Heater alarm, 8: HB alarm, 9: HS alarm, 10: Input error, 11: RSP input error, 12: P.END output*1, 13: RUN output, 14: Integrated alarm, 15: Work bit 1, 16: Work bit 2, 17: Work bit 3, 18: Work bit 4, 19: Work bit 5, 20: Work bit 6, 21: Work bit 7, 22: Work bit 8)
Linear Current Output: H'FFFFFFFB (-5) to H'FFFFFFFF (-1), H'00000000 (0) to H'00000002 (2)
Advanced function setting -
write holding register Control Output 2 Assignment parameter 0x2E07 11783 Control Output 2 Assignment Relay/Voltage Output: H'00000000 (0) to H'00000016 (0 to 22)
Linear Current Output: H'00000000 (0) to H'00000002 (0 to 2)
(Note: Settings are same as Control Output 1, except for items marked with *2 for linear output)
Advanced function setting -

Modbus Register Map (Page 5-10)

type description address in Hex address in decimal parameter name settings / range level default
Write Holding Register (06/16) Event Input Assignment 1 2E0A 11786 Event Input Assignment 1 H'00000000 to H'0000000D (0 to 13) Initial setting 0 (None)
Write Holding Register (06/16) Event Input Assignment 2 2E0B 11787 Event Input Assignment 2 H'00000000 to H'0000000D (0 to 13)
Write Holding Register (06/16) Event Input Assignment 3 2E0C 11788 Event Input Assignment 3 H'00000000 to H'0000000D (0 to 13)
Write Holding Register (06/16) Event Input Assignment 4 2E0D 11789 Event Input Assignment 4 H'00000000 to H'0000000D (0 to 13)
Write Holding Register (06/16) Event Input Assignment 5 2E0E 11790 Event Input Assignment 5 H'00000000 to H'0000000D (0 to 13)
Write Holding Register (06/16) Event Input Assignment 6 2E0F 11791 Event Input Assignment 6 H'00000000 to H'0000000D (0 to 13)
Write Holding Register (06/16) Auxiliary Output 1 Assignment 2E10 11792 Auxiliary Output 1 Assignment H'00000000 to H'00000016 (0 to 22) Advanced function setting 0 (None)
Write Holding Register (06/16) Auxiliary Output 2 Assignment 2E11 11793 Auxiliary Output 2 Assignment H'00000000 to H'00000016 (0 to 22)
Write Holding Register (06/16) Auxiliary Output 3 Assignment 2E12 11794 Auxiliary Output 3 Assignment H'00000000 to H'00000016 (0 to 22)
Write Holding Register (06/16) Auxiliary Output 4 Assignment 2E13 11795 Auxiliary Output 4 Assignment H'00000000 to H'00000016 (0 to 22)
Write Holding Register (06/16) Transfer Output Upper Limit 2E14 11796 Transfer Output Upper Limit H'FFFFF831 to H'0000270F (-1999 to 9999) *2 Initial setting
Write Holding Register (06/16) Transfer Output Lower Limit 2E15 11797 Transfer Output Lower Limit H'FFFFF831 to H'0000270F (-1999 to 9999) *2 Initial setting

Variable Area (Setting Range) List 5-11

type description address in Hex address in decimal parameter name settings / range level default
read/write holding register Simple Transfer Output 1 Upper Limit 2E16 11798 Simple Transfer Output 1 Upper Limit HFFFFF831 to H0000270F (-1999 to 9999) Initial setting
read/write holding register Simple Transfer Output 1 Lower Limit 2E17 11799 Simple Transfer Output 1 Lower Limit HFFFFF831 to H0000270F (-1999 to 9999) Initial setting

Communications Data (Page 5-12)

type description address in Hex address in decimal parameter name settings / range level
Holding Register (03/06/16) Extraction of Square Root Enable 2E24 11812 Extraction of Square Root Enable 0: OFF
1: ON
Initial setting
Holding Register (03/06/16) Travel Time 2E30 11824 Travel Time 1 to 999
Holding Register (03/06/16) Alarm 1 Type 2F00 12032 Alarm 1 Type 0: Alarm function OFF
1: Upper and lower-limit alarm
2: Upper-limit alarm
3: Lower-limit alarm
4: Upper and lower-limit range alarm
5: Upper and lower-limit alarm with standby sequence
6: Upper-limit alarm with standby sequence
7: Lower-limit alarm with standby sequence
8: Absolute-value upper-limit alarm
9: Absolute-value lower-limit alarm
10: Absolute-value upper-limit alarm with standby sequence
11: Absolute-value lower-limit alarm with standby sequence
12: LBA (Loop Burnout Alarm)
13: PV change rate alarm
14: SP absolute-value upper-limit alarm
15: SP absolute-value lower-limit alarm
16: MV absolute-value upper-limit alarm
17: MV absolute-value lower-limit alarm
18: RSP absolute-value upper-limit alarm *
19: RSP absolute-value lower-limit alarm
Valid only with a remote SP input.
Holding Register (03/06/16) Alarm 1 Latch 2F01 12033 Alarm 1 Latch 0: OFF
1: ON
Advanced function setting
Holding Register (03/06/16) Alarm 1 Hysteresis 2F02 12034 Alarm 1 Hysteresis 1 to 9999
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial setting
Holding Register (03/06/16) Alarm 2 Type 2F03 12035 Alarm 2 Type 0 to 19
Note: Same settings as the Alarm 1 Type. However, the LBA (loop burnout alarm) cannot be set.
Holding Register (03/06/16) Alarm 2 Latch 2F04 12036 Alarm 2 Latch 0: OFF
1: ON
Advanced function setting
Holding Register (03/06/16) Alarm 2 Hysteresis 2F05 12037 Alarm 2 Hysteresis 1 to 9999
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial setting
Holding Register (03/06/16) Alarm 3 Type 2F06 12038 Alarm 3 Type 0 to 19
Note: Same settings as the Alarm 1 Type. However, the LBA (loop burnout alarm) cannot be set.
Holding Register (03/06/16) Alarm 3 Latch 2F07 12039 Alarm 3 Latch 0: OFF
1: ON
Advanced function setting
Holding Register (03/06/16) Alarm 3 Hysteresis 2F08 12040 Alarm 3 Hysteresis 1 to 9999
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial setting
Holding Register (03/06/16) Alarm 4 Type 2F09 12041 Alarm 4 Type 0 to 19
Note: Same settings as the Alarm 1 Type. However, the LBA (loop burnout alarm) cannot be set.
Holding Register (03/06/16) Alarm 4 Latch 2F0A 12042 Alarm 4 Latch 0: OFF
1: ON
Advanced function setting
Holding Register (03/06/16) Alarm 4 Hysteresis 2F0B 12043 Alarm 4 Hysteresis 1 to 9999
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial setting
Holding Register (03/06/16) Standby Sequence Reset 2F0C 12044 Standby Sequence Reset 0: Condition A
1: Condition B
Advanced function setting
Holding Register (03/06/16) Auxiliary Output 1 Open in Alarm 2F0D 12045 Auxiliary Output 1 Open in Alarm 0: Close in alarm
1: Open in alarm
Advanced function setting

Variable Area (Setting Range) List (Page 5-13)

type description address in Hex address in decimal parameter name settings / range level
write holding register Auxiliary Output 2 Open in Alarm 2F0E 12046 Auxiliary Output 2 Open in Alarm H'00000000 (0): Close in alarm H'00000001 (1): Open in alarm Advanced function setting
write holding register Auxiliary Output 3 Open in Alarm 2F0F 12047 Auxiliary Output 3 Open in Alarm H'00000000 (0): Close in alarm H'00000001 (1): Open in alarm Advanced function setting
write holding register Auxiliary Output 4 Open in Alarm 2F10 12048 Auxiliary Output 4 Open in Alarm H'00000000 (0): Close in alarm H'00000001 (1): Open in alarm Advanced function setting
write holding register Alarm 1 ON delay 2F11 12049 Alarm 1 ON delay H'00000000 to H'000003E7 (0 to 999)
write holding register Alarm 2 ON delay 2F12 12050 Alarm 2 ON delay H'00000000 to H'000003E7 (0 to 999)
write holding register Alarm 3 ON delay 2F13 12051 Alarm 3 ON delay H'00000000 to H'000003E7 (0 to 999)
write holding register Alarm 4 ON delay 2F14 12052 Alarm 4 ON delay H'00000000 to H'000003E7 (0 to 999)
write holding register Alarm 1 OFF delay 2F15 12053 Alarm 1 OFF delay H'00000000 to H'000003E7 (0 to 999)
write holding register Alarm 2 OFF delay 2F16 12054 Alarm 2 OFF delay H'00000000 to H'000003E7 (0 to 999)
write holding register Alarm 3 OFF delay 2F17 12055 Alarm 3 OFF delay H'00000000 to H'000003E7 (0 to 999)
write holding register Alarm 4 OFF delay 2F18 12056 Alarm 4 OFF delay H'00000000 to H'000003E7 (0 to 999)
write holding register PV/SP No. 1 Display Selection 3000 12288 PV/SP No. 1 Display Selection H'00000000 (0):Nothing displayed.
H'00000001 (1):PV/SP
H'00000002 (2):PV
H'00000003 (3):PV/SP (character display)
H'00000004 (4):PV/SP/MV
H'00000005 (5):PV/SP/Multi-SP No.
H'00000006 (6):PV/SP/Soak time remain
H'00000007 (7):PV/SP/Ramp SP
H'00000008 (8):PV/SP/Alarm value 1
write holding register MV Display Selection 3001 12289 MV Display Selection H'00000000 (0): MV (heating) H'00000001 (1): MV (cooling)
write holding register Automatic Display Return Time 3003 12291 Automatic Display Return Time H'00000000 (0): OFF H'00000001 to H'00000063 (1 to 99)
write holding register Display Refresh Period 3004 12292 Display Refresh Period H'00000000 (0):OFF
H'00000001 (1): 0.25
H'00000002 (2): 0.5
H'00000003 (3): 1.0
write holding register PV/SP No. 2 Display Selection 3008 12296 PV/SP No. 2 Display Selection H'00000000 to H'00000008 (0 to 8) Note: Same as PV/SP No. 1 Display Selection.
write holding register Display Brightness 300A 12298 Display Brightness H'00000001 to H'00000003 (1 to 3)
write holding register MV Display 300B 12299 MV Display H'00000000 (0): OFF H'00000001 (1): ON
write holding register Move to Protect Level Time 300C 12300 Move to Protect Level Time H'00000001 to H'0000001E (1 to 30)
write holding register Auto/Manual Select Addition 300F 12303 Auto/Manual Select Addition H'00000000 (0): OFF H'00000001 (1): ON
write holding register PV Status Display Function 3011 12305 PV Status Display Function H'00000000 (0): OFF
H'00000001 (1): Manual
H'00000002 (2): Stop
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Alarm 1 to 4 OR status
H'00000008 (8): Heater alarm
H'00000009 (9): Status display message*1
write holding register SV Status Display Function 3012 12306 SV Status Display Function H'00000000 to H'00000009 (0 to 9) Note: Same as for PV Status Display Function.

Communications Data (Page 5-14)

type description address in Hex address in decimal parameter name settings / range level default
03 (read) / 06/16 (write) Holding Register Protocol Setting 0C1C 3100 Protocol Setting (See note.) 0: CompoWay/F, 1: Modbus Communications setting
03 (read) / 06/16 (write) Holding Register Communications Unit Number 0C1D 3101 Communications Unit No. * 0 to 99 Communications setting
03 (read) / 06/16 (write) Holding Register Communications Baud Rate 0C1E 3102 Communications Baud Rate * 3: 9.6 kbps, 4: 19.2 kbps, 5: 38.4 kbps, 6: 57.6 kbps Communications setting
03 (read) / 06/16 (write) Holding Register Communications Data Length 0C1F 3103 Communications Data Length * 7: 7 bits, 8: 8 bits Communications setting
03 (read) / 06/16 (write) Holding Register Communications Stop Bits 0C20 3104 Communications Stop Bits * 1: 1 bit, 2: 2 bits Communications setting
03 (read) / 06/16 (write) Holding Register Communications Parity 0C21 3105 Communications Parity * 0: None, 1: Even, 2: Odd Communications setting
03 (read) / 06/16 (write) Holding Register Send Data Wait Time 0C22 3106 Send Data Wait Time * 0 to 99 Communications setting
03 (read) / 06/16 (write) Holding Register PF Setting 0C80 3200 PF Setting 0: Disabled, 1: Run, 2: Stop, 3: RUN/STOP, 4: 100% AT exec/cancel, 5: 40% AT exec/cancel, 6: Alarm latch cancel, 7: Auto/man switch, 8: Mon/set item, 9: Digit shift key Advanced function setting
03 (read) / 06/16 (write) Holding Register Monitor/Setting Item 1 assignment 0C82 3202 Monitor/Setting Item 1 0 to 23 (Selects item to monitor/set, see list in manual: e.g., 0: Disabled, 1: PV/SP/multi-SP, ..., 23: Derivative Time (Cooling)) Advanced function setting
03 (read) / 06/16 (write) Holding Register Monitor/Setting Item 2 assignment 0C83 3203 Monitor/Setting Item 2 0 to 23 (Same options as Item 1) Advanced function setting
03 (read) / 06/16 (write) Holding Register Monitor/Setting Item 3 assignment 0C84 3204 Monitor/Setting Item 3 0 to 23 (Same options as Item 1) Advanced function setting
03 (read) / 06/16 (write) Holding Register Monitor/Setting Item 4 assignment 0C85 3205 Monitor/Setting Item 4 0 to 23 (Same options as Item 1) Advanced function setting
03 (read) / 06/16 (write) Holding Register Monitor/Setting Item 5 assignment 0C86 3206 Monitor/Setting Item 5 0 to 23 (Same options as Item 1) Advanced function setting

Variable Area (Setting Range) List - Page 5-15

type description address in Hex address in decimal parameter name settings / range level default
Read/Write Holding Register SP Tracking 3301 13057 SP Tracking H'00000000 (0): OFF
H'00000001 (1): ON
Advanced function setting 0 (OFF)
Read/Write Holding Register PV Dead Band 3304 13060 PV Dead Band H'00000000 to H'0000270F (0 to 9999) Advanced function setting
Read/Write Holding Register Cold Junction Compensation Method 3305 13061 Cold Junction Comp Method H'00000000 (0): OFF
H'00000001 (1): ON
Advanced function setting 0 (OFF)
Read/Write Holding Register Integral/Derivative Time Unit 3309 13065 Integral/Derivative Unit H'00000000 (0): 1 s
H'00000001 (1): 0.1 s
Advanced function setting 0 (1 s)
Read/Write Holding Register α 330A 13066 α H'00000000 to H'00000064 (0.00 to 1.00) Advanced function setting
Read/Write Holding Register Manual Output Method 330C 13068 Manual Output Method H'00000000 (0): HOLD
H'00000001 (1): INIT
Advanced function setting 0 (HOLD)
Read/Write Holding Register Manual MV Initial Value 330D 13069 Manual MV Initial Value Standard control: HFFFFFFCE to H'0000041A (-5.0 to 105.0)
Heating/cooling: HFFFFFBE6 to H'0000041A (-105.0 to 105.0)
Advanced function setting
Read/Write Holding Register AT Calculated Gain 330F 13071 AT Calculated Gain H'00000001 to H'00000064 (0.1 to 10.0) Advanced function setting
Read/Write Holding Register AT Hysteresis 3310 13072 AT Hysteresis H'00000001 to H'0000270F (0.1 to 999.9 for temp input)
H'00000001 to H'000003E7 (0.01 to 9.99 for analog input)
Advanced function setting
Read/Write Holding Register Limit Cycle MV Amplitude 3311 13073 Limit Cycle MV Amplitude H'00000032 to H'000001F4 (5.0 to 50.0) Advanced function setting
Read/Write Holding Register Heater Burnout Latch 3314 13076 Heater Burnout Latch H'00000000 (0): OFF
H'00000001 (1): ON
Advanced function setting 0 (OFF)
Read/Write Holding Register Heater Burnout Hysteresis 3315 13077 Heater Burnout Hysteresis H'00000001 to H'000001F4 (0.1 to 50.0) Advanced function setting
Read/Write Holding Register HS Alarm Latch 3316 13078 HS Alarm Latch H'00000000 (0): OFF
H'00000001 (1): ON
Advanced function setting 0 (OFF)
Read/Write Holding Register HS Alarm Hysteresis 3317 13079 HS Alarm Hysteresis H'00000001 to H'000001F4 (0.1 to 50.0) Advanced function setting
Read/Write Holding Register Number of Multi-SP Points 331B 13083 Number of Multi-SP Points H'00000002 to H'00000008 (2 to 8) Advanced function setting
Read/Write Holding Register HB ON/OFF 331C 13084 HB ON/OFF H'00000000 (0): OFF
H'00000001 (1): ON
Advanced function setting 0 (OFF)
Read/Write Holding Register Integrated Alarm Assignment 331E 13086 Integrated Alarm Assign H'00000000 to H'000000FF (0 to 255) Advanced function setting
Read/Write Holding Register MV at Stop and Error Addition 3320 13088 MV at Stop/Error Add H'00000000 (0): OFF
H'00000001 (1): ON
Advanced function setting 0 (OFF)
Read/Write Holding Register ST Stable Range 3321 13089 ST Stable Range H'00000001 to H'0000270F (0.1 to 999.9) Advanced function setting
Read/Write Holding Register RT 3322 13090 RT H'00000000 (0): OFF
H'00000001 (1): ON (Valid only with temp input)
Advanced function setting 0 (OFF)
Read/Write Holding Register HS Alarm Use 3323 13091 HS Alarm Use H'00000000 (0): OFF
H'00000001 (1): ON
Advanced function setting 0 (OFF)
Read/Write Holding Register LBA Detection Time 3324 13092 LBA Detection Time H'00000000 to H'0000270F (0 to 9999) Advanced function setting
Read/Write Holding Register LBA Level 3325 13093 LBA Level H'00000001 to H'0000270F (0.1 to 999.9 for temp input)
(0.01 to 99.99 for analog input)
Advanced function setting
Read/Write Holding Register LBA Band 3326 13094 LBA Band H'00000000 to H'0000270F (0.0 to 999.9 for temp input)
(0.00 to 99.99 for analog input)
Advanced function setting
Read/Write Holding Register Soak Time Unit 3327 13095 Soak Time Unit H'00000000 (0): Minutes
H'00000001 (1): Hours
H'00000002 (2): Seconds*1
Advanced function setting 0 (Minutes)
Read/Write Holding Register Alarm SP Selection 3328 13096 Alarm SP Selection H'00000000 (0): Set point during SP ramp
H'00000001 (1): Set point
Advanced function setting 0 (SP ramp)
Read/Write Holding Register Remote SP Enable 3329 13097 Remote SP Enable H'00000000 (0): OFF
H'00000001 (1): ON
Advanced function setting 0 (OFF)
Read/Write Holding Register Manual MV Limit Enable 332B 13099 Manual MV Limit Enable H'00000000 (0): OFF
H'00000001 (1): ON
Advanced function setting 0 (OFF)
Read/Write Holding Register Direct Setting of Position Prop MV 332C 13100 Direct Setting Prop MV H'00000000 (0): OFF
H'00000001 (1): ON
Advanced function setting 0 (OFF)
Read/Write Holding Register PV Rate of Change Calc Period 332D 13101 PV Rate Change Period H'00000001 to H'000003E7 (1 to 999) Advanced function setting

Communications Data for Modbus (Page 5-16)

type description address in Hex address in decimal parameter name settings / range level default
Holding Register (03/06/16) Heating/Cooling Tuning Method 332E 13102 Heating/Cooling Tuning Method H'00000000 (0): Same as heating control.
H'00000001 (1): Linear
H'00000002 (2): Air cooling
H'00000003 (3): Water cooling
Advanced function setting -
Holding Register (03/06/16) LCT Cooling Output Minimum ON Time (Not supported on version 2.0 or earlier of the E5CC, E5EC, or E5AC.) 3335 13109 LCT Cooling Output Minimum ON Time H'00000001 to H'0000000A (0.1 to 1.0) - -