3.3 KiB
Omron MX2
- Please refer to the OmronMX2 - Modbus setup guide(Section 7.2.2)
In case the terminal labels mismatch the documenation, please use SN for (A-) and SP for (B+)
1.1 Set basic parameters
- Max. Frequency, depending on gearbox, A004 = 75Hz
- Acceleration time, F02 = 2secs
- Decceleration time, F03 = 2secs
- The firmware expects the VFD at Slave-Address 1 !
Additionally, please check the user manual
2.1 Modbus settings - Page 297
- Parity : None -
C74= 00 - Speed : 9600 -
C71= 5 (6=19200) see manual - Page 167 - Slave Id : 1 -
C72= 1
2.2 Control settings
- Frequency selection -
A001: 03 (Modbus) - Command selection -
A002: 03 (Modbus)
Please restart the inverter after changing those settings!
2.3 Test settings, using serial Modbus adapter CP2102 and Modbus poll (see ./tools/MbPoll_v9.4.0_cracked.exe)
2.3.1 Wire the CP2102 USB adapter
2.3.2 Connect
2.3.3 Function - Write Coil
The 'Run' LED shoud now be on.
Omron E5 - PID
TCP interface
To set the target temperature to 100 Degc on PID1, the complete message for Modbus TCP would be
01 06 00 11 00 64 D8 24
01: slave id06: Modbus verb / function code, in this case WRITE HOLDING REGISTER11: address (17)00 64: value (100), 2 bytesD8 24: CRC, 2 bytes. Since it's TCP, this isn't evaluated and can be ignored on the Controllino - PlasticHub firmware (see './firmware/Mudbus.cpp').
In order to fake a Modbus message, all we need is 01 06 00 11 00 64 but we also have to prefix it with the TCP overhead (d2 8d 00 00 00 06)
|-- TCP Overhead----- | -------- Modbus ---- |
d2 8d 00 00 00 06 | 01 06 00 11 00 64
In example, we can send this via Hercules :
The TCP overhead (d2 8d 00 00 00 06) is created as follow:
d2 8d: Transaction identifier, 2 bytes00 00: Protocol identifier, 2 bytes00 06: Length of the message, 2 bytes
Modbus Registers - Controllino Mega (Master)
Write - Register
1: VFD - Target Freq3: VFD - Status- OMRON_STATE_ACCELERATING 4
- OMRON_STATE_DECELERATING 2
- OMRON_STATE_RUNNING 3
- OMRON_STATE_STOPPED 1
- OMRON_STATE_ERROR 8
5: VFD - Start:01 / Stop:026: VFD - Frequency7: VFD - Direction - Forward : 1 | Reverse : 2 | Stop : 3
Misc
Firmware update using command line
C:\Program Files (x86)\arduino-1.6.10\hardware\tools\avr/bin/avrdude -CC:\Program Files (x86)\arduino-1.6.10\hardware\tools\avr/etc/avrdude.conf -v -patmega328p -carduino -PCOM21 -b115200 -D -Uflash:w:C:\Users\per\AppData\Local\Temp\builda0905d717cd3fb20c5f6c59067701315.tmp/serial.ino.hex:i