# VFD
## Start & Stop
Starts or stops the VFD, be aware that a target frequency has to be set as well
- **Address** : 5
- **Function** : 6 (WRITE_REGISTER)
- **Values** :
- **On** : 1
- **Off** : 2
**TCP Sequence for Start**
```c
d2 8d 00 00 00 06 01 06 00 05 00 01
+ + + +
| | | |
| | | +----> Value (2 bytes) = 00 01
| | |
| | +----> Address (2 bytes) = 05 or 0x0005
| |
| +--> Function Code (Always 6)
|
+--> Slave - ID (Always 1)
```
**TCP Sequence for Stop**
```c
d2 8d 00 00 00 06 01 06 00 05 00 02
+ + + +
| | | |
| | | +----> Value (2 bytes) = 00 02
| | |
| | +----> Address (2 bytes) = 05 or 0x0005
| |
| +--> Function Code (Always 6)
|
+--> Slave - ID (Always 1)
```
## Frequency
Sets the target frequency
- **Address** : 6
- **Function** : 6 (WRITE_REGISTER)
- **Values** : 1 - 50
**TCP Sequence for setting target frequency to 50 Hz**
Remark : Please respect the max. main frequency setting on the inverter (settings)
```c
d2 8d 00 00 00 06 01 06 00 05 00 32
+ + + +
| | | |
| | | +----> Value (2 bytes) = 00 32 (for 50Hz)
| | |
| | +----> Address (2 bytes) = 06 or 0x0006
| |
| +--> Function Code (Always 6)
|
+--> Slave - ID (Always 1)
```
## Direction
Sets the rotation
- **Address** : 7
- **Function** : 6 (WRITE_REGISTER)
- **Values** :
- **Forward** : 1
- **Reverse** : 2
- **Stop** : 3
**TCP Sequence for setting direction : Forward**
```c
d2 8d 00 00 00 06 01 06 00 07 00 01
+ + + +
| | | |
| | | +----> Value (2 bytes) = 00 01
| | |
| | +----> Address (2 bytes) = 07 or 0x0006
| |
| +--> Function Code (Always 6)
|
+--> Slave - ID (Always 1)
```
**TCP Sequence for setting direction : Reverse**
```c
d2 8d 00 00 00 06 01 06 00 07 00 02
+ + + +
| | | |
| | | +----> Value (2 bytes) = 00 02
| | |
| | +----> Address (2 bytes) = 07 or 0x0006
| |
| +--> Function Code (Always 6)
|
+--> Slave - ID (Always 1)
```