### Omron MX2
|
|
|
|
1. Please refer to the [OmronMX2 - Modbus setup guide](../vendor/omron/P641-E1-01_EGuide_CJ_Mod485_OMRON_3G3MX2-V1.pdf)(Section 7.2.2)
|
|
|
|
In case the terminal labels mismatch the documenation, please use `SN` for (A-) and `SP` for (B+)
|
|
|
|
2. The firmware expects the VFD at **Slave-Address 10** !
|
|
|
|
Additionally, please check the [user manual](../vendor/omron/I570-E2-02B.pdf)
|
|
|
|
### Omron E5 - PID
|
|
|
|
### TCP interface
|
|
|
|
To set the target temperature to 100 Degc on PID1, the complete message for Modbus TCP would be
|
|
|
|

|
|
|
|
``` 01 06 00 11 00 64 D8 24 ```
|
|
|
|
- ```01``` : slave id
|
|
- ```06``` : Modbus verb / function code, in this case **WRITE HOLDING REGISTER**
|
|
- ```11``` : address (17)
|
|
- ```00 64``` : value (100), 2 bytes
|
|
- ```D8 24``` : CRC, 2 bytes. Since it's TCP, **this isn't evaluated and can be ignored** on the Controllino - PlasticHub firmware (see ['./firmware/Mudbus.cpp'](./firmware/Mudbus.cpp)).
|
|
|
|
In order to fake a Modbus message, all we need is ``` 01 06 00 11 00 64``` but we also have to prefix it with the TCP overhead (d2 8d 00 00 00 06)
|
|
|
|
|-- TCP Overhead----- | -------- Modbus ---- |
|
|
|
|
**```d2 8d 00 00 00 06 ```** | ```01 06 00 11 00 64```
|
|
|
|
In example, we can send this via Hercules :
|
|
|
|

|
|
|
|
The TCP overhead (```d2 8d 00 00 00 06```) is created as follow:
|
|
|
|
- ```d2 8d``` : Transaction identifier, 2 bytes
|
|
- ```00 00``` : Protocol identifier, 2 bytes
|
|
- ```00 06``` : Length of the message, 2 bytes
|