mono/packages/kbot/tests/pdf/omron/modbus.md
2025-04-24 17:52:34 +02:00

36 KiB

No registers found, Page Number 4-13

Variable Area (Setting Range) List (Page 5-2)

type description address in Hex address in decimal parameter name settings / range level default
FC 03 / FC 16 Process Value (PV) 2000 8192 PV Temperature/Analog specific range (See manual) Operation
FC 03 / FC 16 Status 2001 8193 Status 12 Refer to 5-2 Status for details Operation
FC 03 / FC 16 Internal Set Point 2002 8194 Internal Set Point *1 SP lower limit to SP upper limit Operation
FC 03 / FC 16 Heater Current 1 Value Monitor 2003 8195 Heater Current 1 Value Monitor 0.0 to 55.0 (H'00000000 to H'00000226) Operation
FC 03 / FC 16 MV Monitor (Heating) 2004 8196 MV Monitor (Heating) -5.0 to 105.0 (Standard: HFFFFFFCE to H'0000041A) Operation
FC 03 / FC 16 MV Monitor (Cooling) 2005 8197 MV Monitor (Cooling) 0.0 to 105.0 (Heating/Cooling: H'00000000 to H'0000041A) Operation
FC 03 / FC 16 Set Point 2103 8451 Set Point SP lower limit to SP upper limit Operation
FC 03 / FC 16 Alarm Value 1 2104 8452 Alarm Value 1 -1999 to 9999 (HFFFFFF831 to H'0000270F) Operation
FC 03 / FC 16 Alarm Value Upper Limit 1 2105 8453 Alarm Value Upper Limit 1 -1999 to 9999 (HFFFFFF831 to H'0000270F) Operation
FC 03 / FC 16 Alarm Value Lower Limit 1 2106 8454 Alarm Value Lower Limit 1 -1999 to 9999 (HFFFFFF831 to H'0000270F) Operation
FC 03 / FC 16 Alarm Value 2 2107 8455 Alarm Value 2 -1999 to 9999 (HFFFFFF831 to H'0000270F) Operation
FC 03 / FC 16 Alarm Value Upper Limit 2 2108 8456 Alarm Value Upper Limit 2 -1999 to 9999 (HFFFFFF831 to H'0000270F) Operation
FC 03 / FC 16 Alarm Value Lower Limit 2 2109 8457 Alarm Value Lower Limit 2 -1999 to 9999 (HFFFFFF831 to H'0000270F) Operation
FC 03 / FC 16 Process Value (PV) 2402 9218 PV Temperature/Analog specific range (See manual) Operation
FC 03 / FC 16 Internal Set Point 2403 9219 Internal Set Point *1 SP lower limit to SP upper limit Operation
FC 03 / FC 16 Multi-SP No. Monitor 2404 9220 Multi-SP No. Monitor 0 to 7 (H'00000000 to H'00000007) Operation
FC 03 / FC 16 Status 2406 9222 Status 12 Refer to 5-2 Status for details Operation
FC 03 / FC 16 Status 2407 9223 Status *3 Refer to 5-2 Status for details Operation
FC 03 / FC 16 Status 2 2408 9224 Status 2 12 Refer to 5-2 Status for details Operation
FC 03 / FC 16 Status 2 2409 9225 Status 2 13 Refer to 5-2 Status for details Operation
FC 03 / FC 16 Decimal Point Monitor 2410 9232 Decimal Point Monitor 0 to 3 (H'00000000 to H'00000003) Operation

Variable Area (Setting Range) List (Page 5-3)

type description address in Hex address in decimal parameter name settings / range level default
holding register Operation/Adjustment Protect H'0500 2500 Operation/Adjustment Protect H'00000000 (0): No restrictions in operation and adjustment levels
H'00000001 (1): Move to adjustment level is prohibited.
H'00000002 (2): Display and change of only "PV" and "PV/SP" parameters is allowed.
H'00000003 (3): Display of only "PV" and "PV/SP" parameters is allowed.
Protect H'00000000
holding register Initial Setting/Communications Protect H'0502 2501 Initial Setting/Comm Protect H'00000000 (0): Move to initial setting/communications setting level is allowed. (Move to advanced function setting level is displayed.)
H'00000001 (1): Move to initial setting/communications setting level is allowed. (Move to advanced function setting level is not displayed.)
H'00000002 (2): Move to initial setting/communications setting level is prohibited.
H'00000000
holding register Setting Change Protect H'0504 2502 Setting Change Protect H'00000000 (0): OFF (Changing of setup on controller display is allowed.)
H'00000001 (1): ON (Changing of setup on controller display is prohibited.)
H'00000000
holding register PF Key Protect H'0506 2503 PF Key Protect H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000
holding register Move to Protect Level H'0508 2504 Move to Protect Level H'FFFFF831 to H'0000270F (-1999 to 9999)
holding register Password to Move to Protect Level H'050A 2505 Password to Move Protect Lvl H'FFFFF831 to H'0000270F (-1999 to 9999) (Can only be set. The monitor value is always H'00000000.) H'00000000
holding register Parameter Mask Enable H'050C 2506 Parameter Mask Enable H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000
holding register Changed Parameters Only H'050E 2507 Changed Parameters Only H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000
holding register Manual MV H'0600 2600 Manual MV Standard Models:
Standard control: H'FFFFFCE to H'0000041A (-5.0 to 105.0)
Heating and cooling control: H'FFFFFBE6 to H'0000041A (-105.0 to 105.0)
Position-proportional Models:
Close position-proportional control with the Direct Setting of Position Proportional MV parameter set to ON: H'FFFFFCE to H'0000041A (-5.0 to 105.0)
Manual control
holding register Set Point H'0602 2601 Set Point SP lower limit to SP upper limit Operation
holding register Remote SP Monitor H'0604 2602 Remote SP Monitor Remote SP lower limit -10% FS to Remote SP upper limit +10% FS
holding register Heater Current 1 Value Monitor H'0608 2604 Heater Current 1 Value Mon H'00000000 to H'00000226 (0.0 to 55.0)
holding register MV Monitor (Heating) H'060A 2605 MV Monitor (Heating) Standard control: H'FFFFFCE to H'0000041A (-5.0 to 105.0)
Heating and cooling control: H'00000000 to H'0000041A (0.0 to 105.0)
holding register MV Monitor (Cooling) H'060C 2606 MV Monitor (Cooling) H'00000000 to H'0000041A (0.0 to 105.0)
holding register Valve Opening Monitor H'060E 2607 Valve Opening Monitor H'FFFFF9C to H'0000044C (-10.0 to 110.0)

Communications Data for Modbus (Page 5-4)

type description address in Hex address in decimal parameter name settings / range level default
Read/Write Holding Register Proportional Band (Cooling) 0701 1793 Proportional Band (Cooling) H'00000001 to H'0000270F (0.1 to 999.9) Adjustment
Read/Write Holding Register Integral Time (Cooling) 0702 1794 Integral Time (Cooling) H'00000000 to H'0000270F (0 to 9999: Integral/derivative time unit is 1 s.) (0.0 to 999.9: Integral/derivative time unit is 0.1 s.) Adjustment
Read/Write Holding Register Derivative Time (Cooling) 0703 1795 Derivative Time (Cooling) H'00000000 to H'0000270F (0 to 9999: Integral/derivative time unit is 1 s.) (0.0 to 999.9: Integral/derivative time unit is 0.1 s.) Adjustment
Read/Write Holding Register Dead Band 0704 1796 Dead Band H'FFFFF831 to H'0000270F (-199.9 to 999.9 for temperature input) (-19.99 to 99.99 for analog input) Adjustment
Read/Write Holding Register Manual Reset Value 0705 1797 Manual Reset Value H'00000000 to H'000003E8 (0.0 to 100.0) Adjustment
Read/Write Holding Register Hysteresis (Heating) 0706 1798 Hysteresis (Heating) H'00000001 to H'0000270F (0.1 to 999.9 for temperature input) (0.01 to 99.99 for analog input) Adjustment
Read/Write Holding Register Hysteresis (Cooling) 0707 1799 Hysteresis (Cooling) H'00000001 to H'0000270F (0.1 to 999.9 for temperature input) (0.01 to 99.99 for analog input) Adjustment
Read/Write Holding Register Control Period (Heating) 0708 1800 Control Period (Heating) H'FFFFFFFE (-2): 0.1 s H'FFFFFFFF (-1): 0.2 s H'00000000 (0): 0.5 s H'00000001 to H'00000063 (1 to 99) Initial setting
Read/Write Holding Register Control Period (Cooling) 0709 1801 Control Period (Cooling) H'FFFFFFFE (-2): 0.1 s H'FFFFFFFF (-1): 0.2 s H'00000000 (0): 0.5 s H'00000001 to H'00000063 (1 to 99) Initial setting
Read/Write Holding Register Position Proportional Dead Band 070A 1802 Position Proportional Dead Band H'00000001 to H'00000064 (0.1 to 10.0) Adjustment
Read/Write Holding Register Open/Close Hysteresis 070B 1803 Open/Close Hysteresis H'00000001 to H'000000C8 (0.1 to 20.0) Adjustment
Read/Write Holding Register SP Ramp Time Unit 070C 1804 SP Ramp Time Unit H'00000000 (0): EU/second H'00000001 (1): EU/minute H'00000002 (2): EU/hour Advanced function setting
Read/Write Holding Register SP Ramp Set Value 070D 1805 SP Ramp Set Value H'00000000 (0): OFF H'00000001 to H'0000270F (1 to 9999) Adjustment
Read/Write Holding Register SP Ramp Fall Value 070E 1806 SP Ramp Fall Value H'FFFFFFFF (-1): Same (Same as SP Ramp Set Value.) H'00000000 (0): OFF H'00000001 to H'0000270F (1 to 9999) Adjustment
Read/Write Holding Register MV at Stop 070F 1807 MV at Stop Standard Models: Standard control: H'FFFFFCE to H'0000041A (-5.0 to 105.0) Heating and cooling control: H'FFFFFBE6 to H'0000041A (-105.0 to 105.0) Position-proportional Models: Close position-proportional control with the Direct Setting of Position Proportional MV parameter set to ON: H'FFFFFCE to H'0000041A (-5.0 to 105.0) Floating position-proportional control or the Direct Setting of Position Proportional MV parameter set to OFF: H'FFFFFFFF to H'00000001 (-1 to 1) Adjustment
Read/Write Holding Register MV at PV Error 0711 1809 MV at PV Error Same as MV at Stop parameter Adjustment
Read/Write Holding Register MV Change Rate Limit 0713 1811 MV Change Rate Limit H'00000000 to H'000003E8 (0.0 to 100.0) Operation
Read/Write Holding Register PV Input Slope Coefficient 0718 1816 PV Input Slope Coefficient H'00000001 to H'0000270F (0.001 to 9.999) Operation
Read/Write Holding Register Heater Current 1 Value Monitor 071A 1818 Heater Current 1 Value Monitor H'00000000 to H'00000226 (0.0 to 55.0) Operation
Read/Write Holding Register Heater Burnout Detection 1 071B 1819 Heater Burnout Detection 1 H'00000000 to H'000001F4 (0.0 to 50.0) Adjustment
Read/Write Holding Register Leakage Current 1 Monitor 071C 1820 Leakage Current 1 Monitor H'00000000 to H'00000226 (0.0 to 55.0) Operation
Read/Write Holding Register HS Alarm 1 071D 1821 HS Alarm 1 H'00000000 to H'000001F4 (0.0 to 50.0) Adjustment
Read/Write Holding Register Process Value Input Shift 0723 1827 Process Value Input Shift H'FFFFF831 to H'0000270F (-1999 to 9999) Adjustment
Read/Write Holding Register Heater Current 2 Value Monitor 0724 1828 Heater Current 2 Value Monitor H'00000000 to H'00000226 (0.0 to 55.0) Operation

Variable Area (Setting Range) List (Page 5-5)

type description address in Hex address in decimal parameter name settings / range level default
Write Holding Register (FC 06/16) Heater Burnout Detection 2 2725 10021 Heater Burnout Detection 2 H'00000000 to H'000001F4 (0.0 to 50.0) Adjustment
Write Holding Register (FC 06/16) Leakage Current 2 Monitor 2726 10022 Leakage Current 2 Monitor H'00000000 to H'00000226 (0.0 to 55.0) Operation
Write Holding Register (FC 06/16) HS Alarm 2 2727 10023 HS Alarm 2 H'00000000 to H'000001F4 (0.0 to 50.0) Adjustment
Write Holding Register (FC 06/16) Soak Time Remain 2728 10024 Soak Time Remain H'00000000 to H'0000270F (0 to 9999) Operation
Write Holding Register (FC 06/16) Soak Time 2729 10025 Soak Time H'00000001 to H'0000270F (1 to 9999) Adjustment
Write Holding Register (FC 06/16) Wait Band 272A 10026 Wait Band H'00000000 (0): OFF, H'00000001 to H'0000270F (0.1 to 999.9 for Temp input / 0.01 to 99.99 for Analog input) Adjustment OFF
Write Holding Register (FC 06/16) Remote SP Input Shift 272B 10027 Remote SP Input Shift H'FFFFF831 to H'0000270F (-1999 to 9999) Advanced function setting
Write Holding Register (FC 06/16) Remote SP Input Slope Coefficient 272C 10028 Remote SP Input Slope Coefficient H'00000001 to H'0000270F (0.001 to 9.999) Advanced function setting
Write Holding Register (FC 06/16) Input Digital Filter 2800 10240 Input Digital Filter H'00000000 to H'0000270F (0.0 to 999.9) Advanced function setting
Write Holding Register (FC 06/16) Moving Average Count 2804 10244 Moving Average Count H'00000000 (0): OFF, H'00000001 (1): 2 times, H'00000002 (2): 4 times, H'00000003 (3): 8 times, H'00000004 (4): 16 times, H'00000005 (5): 32 times Advanced function setting OFF